Adjustable flow rate at 100 – 200 – 300 – 400 l/min.
Flush function for up to 6mm size impurities cleaning.
Weight ~ 2,3 kg (adapter included).
Maximum spray jet 160° for user protection against Flashover.
This nozzle can be used to put out an electrical fire up to a voltage of 380 kV with spray jet.
Smooth settings adjustment between spray jet and maximum spray jet - within maximum range of 160°. The most outer setting position allows to switch to the maximum spray jet for user protection against Flashover.
Turbo Master nozzle operating at 6 bar with water flow 400 l/min, breaks up water into droplets of approx. 0.45 mm. Higher pressure and/or lower water flow allows to reduce the droplet size to approx. 0.2 mm. At the maximum flow rate the water jet provides sufficient protection against the effect of "high voltage flash-over" up to 380 kV as required by DIN VDE 0132 at spray jet.